Heat transfer and exergy loss in conical spring turbulators
Yükleniyor...
Tarih
2013-05
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Elsevier
Erişim Hakkı
info:eu-repo/semantics/restrictedAccess
Attribution-NonCommercial-ShareAlike 3.0 United States
Attribution-NonCommercial-ShareAlike 3.0 United States
Özet
It would be misleading to consider only the construction costs of heat exchangers in their design because high service costs during their service life may also greatly increase total costs. Therefore energy saving aspects are very important in the design, construction and operation of the heat exchangers. For this reason, various active or passive methods have been sought to save energy by increasing the heat transfer coefficients in the cold and warm fluid sides in the heat exchangers. Conical spring turbulators (CST) are devised in this study. Performances of heat transfer and pressure drop in a pipe with the CST are experimentally examined for the CSTs’ angle (θ) of 30°, 45° and 60° in Reynolds number (Re) range of 10,000–34,000. Heat transfer, pressure loss and exergy analysis were made for the conditions with and without turbulators and compared to each other. Some empirical correlations expressing the results were also derived and discussed.
Açıklama
Anahtar Kelimeler
Turbulators, Concentric Heat Exchanger, Exergy Loss, NTU
Kaynak
WoS Q Değeri
Q1
Scopus Q Değeri
Q1
Cilt
60
Sayı
Künye
Karakaya, H., Durmuş, A. (2013). Heat transfer and exergy loss in conical spring turbulators. International Journal of Heat and Mass Transfer, 60, pp.756-762. DOI:http://dx.doi.org/10.1016/j.ijheatmasstransfer.2013.01.054